ANALISIS PEMASANGAN AUTOMATIC METER READING (AMR) SEBAGAI PENDETEKSI AWAL KELAINAN ALAT PENGUKUR DAN PEMBATAS (APP) PADA PELANGGAN BESAR DI PT.PLN (PERSERO) RAYON SUBULUSSALAM KOTA

Sepannur Bandri, Zuriman Anthony, Rifky Rifky

Sari


Measuring electrical energy is an important matter between PLN and its customers. For this reason, PLN uses kWh meters as a tool to measure energy usage for customers. However, the kWh meter used must not only be able to measure, but must also be accurate, precise and easy. Especially for large customers, where special attention is needed for the use of electrical energy. For this reason, PLN has implemented electronic meters that have been installed with the AMR system for large customers. This is intended so that historical electricity usage for large customers can be recorded and monitored properly. Apart from that, the AMR system is also useful as an early detection of abnormalities in electronic meters for large customers by analyzing the data obtained. Through this data, DLPD (List of Subscriptions Needing Attention) can be determined so that customers who experience problems with their electronic meters can be monitored. With this DLPD feature, it really helps PLN employees in analyzing and evaluating the disturbances that occur.

 

Keywords: Automatic Meter Reading, Electronic Meter, DLPD, AMICON


Teks Lengkap:

PDF

Referensi


Arifin, Y. R. (2020). Dilematika Kebijakan Ketenagalistrikan Dalam Usaha Penyediaan Tenaga Listrik di Indonesia. Jurnal Ius Constituendum, 6(1), 1-31.

Marsudi, Djiteng, 2006, Operasi Sistem Tenaga Listrik, Yogyakarta, Graha Ilmu.

Supriyanto, Eko, 2013, Analisa Vektor, Kuadran, dan Load Profile, Pandaan, PLN Pusdiklat.

Amru, A. A., Sara, I. D., & Syahrizal, S. (2021). Manajemen Pemakaian Pulsa Listrik Pelanggan Meter Prabayar. Jurnal Komputer, Informasi Teknologi, dan Elektro, 6(1).

Rahmadhani, S. N. (2018). Evaluasi Efektivitas Pengendalian Internal Akuntansi Atas Jaringan Distribusi Listrik Oleh PT PLN (Persero) Studi Kasus: Di Sumatera Utara. Jurnal Akuntansi Dan Bisnis: Jurnal Program Studi Akuntansi, 4(2), 24-30.

Supriyanto, Eko, 2013, Analisa Penyebab Kegagalan Baca, Pandaan, PLN Pusdiklat.

AKBAR, M. (2022). PENGGUNAAN SISTEM AMR (AUTOMATIC METER READING) DALAM PENDETEKSIAN KELAINAN PADA PENGUKURAN ENERGI LISTRIK DI PT. PLN (PERSERO) UP3 PALEMBANG (Doctoral dissertation, Politeknik Negeri Sriwijaya).

Kale, A. C., Sirait, D. F. R., Rizal, M. F., Huda,

I. F., Al Farisi, M. S., Siregar, F. P., ... & Saputra, O. R. H. Y. (2024). Pengaruh Variasi Tegangan dan Arus pada KWh Meter Mekanik dan Digital Satu Fasa di Sekitar Cempakasari. Jurnal Majemuk, 3(1), 32-46. Mismail, Budiono, 1995, Rangkaian Listrik, Bandung, Penerbit ITB.

Sudirham, Supriyadi, 2002, Analisis Rangkaian Listrik, Bandung , Penerbit ITB.

Santika, Gora Anadi, M. Sobarsyah, and Dian AS Parawansa. "Model Asesmen Berbasis Indeks dalam Pengelolaan Material Transmisi Utama pada PT PLN (Persero) UIKL Sulawesi: Mini Review." Management Dynamics Conference 8. Vol. 8. No. 1. 2023.

Yulisa, sukmawati. "prosedur pengadaan alat tulis kantor sub bidang aset properti dan umum pada pt pln (persero) unit induk distribusi lampung." (2023).

Agustina, Ellisa, and Alvina Fitri Amalia. "Penurunan susut non teknis pada jaringan distribusi menggunakan sistem automatic meter reading di pt. pln (persero)." Jurnal Teknologi Elektro 8.1 (2017): 142273.

AROFA, A. N. (2022). ANALISA PENGARUH PEMASANGAN AMR PADA PELANGGAN PT PLN UP3 PALEMBANG TERHADAP SUSUT NON-TEKNIS (Doctoral dissertation, Politeknik Negeri Sriwijaya).

Muhammad, Thariq. "Automatic Meter Reading (AMR) System di PT. PLN (Persero) Unit Pelaksana Pelayanan Pelanggan (UP3) Padang." (2023).

Sulistiyawati Dewi, K., Mursyidan, A., & Fatimah, I. Rangkaian Seri RLC Arus AC (E7). Amalia, A. M. (2010). Pengaruh kuat medan magnet dan kecepatan rotor terhadap tegangan yang dihasilkan generator arus bolak-balik leybold tps 2.5.

Darma, S., Yusmartato, Y., & Akhiruddin, A. (2019). Studi sistem peneraan kWh meter. JET (Journal of Electrical Technology), 4(3), 158-165.

Lukman, F. S., Mubarak, H., & Hasibuan, A. (2022). Power Bank kWh Meter Automatic Meter Reading. RELE (Rekayasa Elektrikal Dan Energi): Jurnal Teknik Elektro, 4(2), 129-133.

Asmono, D. (2019). Pengukuran energi listrik tidak langsung menggunakan KWH meter dan kvarh meter. Jurnal TEDC, 8(3), 198-204.

Fahmi, E., & Permana, Y. (2015). Sistem Automatic Meter Reading Bulanan Melalui Sms Berbasis Mikrokontroler. Journal Ict, 6(11).

AMANI, I. (2021). EVALUASI LOAD PROFILE PADA KWH METER DENGAN MENGGUNAKAN SISTEM AUTOMATIC METER READING (AMR) DI PT PLN (PERSERO) UP3 PALEMBANG (Doctoral dissertation, Politeknik Negeri Sriwijaya). Heriyanto, A. (2016). Studi Kasus Kinerja AMR (Automatic Meter Reading) Pada Pelanggan Potensial Daya 41.5 KVA–200 KVA Di Situbondo. Jurnal Teknik Elektro Universitas Muhammadiyah Jember, 1.

WAHYUNI, I. (2022). PENGARUH KETIDAKNORMALAN PENGAWATAN METER ELEKTRONIK DENGAN SISTEM AUTOMATIC METER READING (AMR) DI PT PLN (PERSERO) UP3 OGAN ILIR (Doctoral dissertation, Politeknik Negeri Sriwijaya). Wiharja, U., & Albahar, A. K. (2018). Analisa Deteksi Ketidaknormalan Meter Elektronik Dengan Sistem Automatic Meter Reading. Prosiding Semnastek.

Kapora, N. (2019). ANALISA SIMULASI DIAGRAM PHASOR PADA APLIKASI AMICON UNTUK MENGETAHUI PEMBACAAN KWH METER TERHADAP KERUSAKAN CURRENT TRANSFORMATOR DAN POTENSIAL TRANSFORMATOR (Doctoral dissertation, Politeknik Negeri Sriwijaya).

PRILIANSYAH, R. (2023). PENURUNAN SUSUT NON TEKNIS DENGAN METODE ANALISA LOAD PROFILE DAN JAM NYALA PELANGGAN BERBASIS AMR (Doctoral dissertation, Universitas Mercu Buana Jakarta). Amalia, A. M. (2010). Pengaruh kuat medan magnet dan kecepatan rotor terhadap tegangan yang dihasilkan generator arus bolak-balik leybold tps 2.5.

Sukmadi, T., & Winardi, B. (2009). Perhitungan Dan Analisis Keseimbangan Beban Pada Sistem Distribusi 20 Kv Terhadap Rugi-Rugi Daya (Studi Kasus Pada Pt. Pln Upj Slawi). Transmisi: Jurnal Ilmiah Teknik Elektro, 11(1), 47-52.

Noor, F. A., Ananta, H., & Sunardiyo, S. (2017). Pengaruh Penambahan Kapasitor Terhadap tegangan, arus, faktor daya, dan daya aktif pada beban listrik di minimarket. Jurnal Teknik Elektro, 9(2), 66-73.

Handarly, D., & Lianda, J. (2018). Sistem Monitoring Daya Listrik Berbasis IoT (Internet of Thing). J. Electr. Electron. Control Automot. Eng, 3(2), 205-208.

Kuswanto, H. (2010). Alat ukur listrik ac (arus, tegangan, daya) dengan port paralel.

Martias, M. (2017). Penerapan Dan Penggunaan Alat Ukur Multimeter Pada Pengukuran Komponen Elektronika. Konferensi Nasional Ilmu Sosial dan Teknologi, 1(1).

Martias, M. (2017). Penerapan Dan Penggunaan Alat Ukur Multimeter Pada Pengukuran Komponen Elektronika. Konferensi Nasional Ilmu Sosial dan Teknologi, 1(1).

PUTRI, N. A. R. P. (2019). ANALISA PEMANTAUAN PEMAKAIAN ENERGI LISTRIK PADA PELANGGAN POTENSIAL DENGAN MENGGUNAKAN SISTEM AMR (AUTOMATIC METER READING) DI PT. PLN (PERSERO) UP3 PALEMBANG (Doctoral dissertation, Politeknik Negeri Sriwijaya).

AMANI, I. (2021). EVALUASI LOAD PROFILE PADA KWH METER DENGAN MENGGUNAKAN SISTEM AUTOMATIC METER READING (AMR) DI PT PLN (PERSERO) UP3 PALEMBANG (Doctoral dissertation, Politeknik Negeri Sriwijaya).

Surusa, F. E. P., Humena, S., & Nani, F. Y. (2022). Analisa Susut Non Teknis Menggunakan Automatic Meter Reading (AMR) Pada Pelanggan Potensial. Jambura Journal of Electrical and Electronics Engineering, 4(1), 1-7.




DOI: https://doi.org/10.33559/eoj.v7i3.3067

Refbacks

  • Saat ini tidak ada refbacks.


Jumlah Kunjungan

Negara Pengunjung

Flag Counter

Lisensi Creative Commons
Ciptaan disebarluaskan di bawah Lisensi Creative Commons Atribusi 4.0 Internasional.